300/500 V LSZH insulated steel wire braided LSZH sheathed flexible cables.
| Construction | Cu/LSZH /LSZH /GSWB/LSZH |
| Certification / Standard | VDE 0250-214 and TSE K 176 |
| Application Area |
Used in measurement , control and regulation equipments, conveyors, manufacturing lines, connection of computers. It is convenient to used in middle-mechanic conditions. |
| Max. operating temperature | + 70°C |
| Max. curcuit temperature | 160⁰ C |
| Min. bending radius | 12xD |
| NominalCross Section(mm2) | Overall Diameter (mm) | Net Weight(kg/km) approx. | Conductor DC resistance at 20⁰C(ohm/km)max. | Current Carrying capacity |
|---|---|---|---|---|
| Air (A) | ||||
| 3x1,5 | 8,6 | 143 | 13,3 | 20 |
| 4x1,5 | 9,3 | 170 | 13,3 | 20 |
| 3x2,5 | 9,9 | 190 | 7,98 | 26 |
| 4x2,5 | 10,8 | 240 | 7,98 | 26 |
| 3x4 | 12,2 | 323 | 4,95 | 33 |
| 3x6 | 13,4 | 343 | 3,30 | 44 |